N2XH (CONTROL)

0.6/1 kV ,Multi core ,Solid or Stranded copper conductor, XLPE insulation, Halogen Free , Flame Retardant Cables LV Power Cable

Standart
TS HD 604 S1 , VDE 0276

Technical Data 

Max.Operating Temperature: 90 ° C

Max.Short Circuit Temperature: 250 ° C

Rated Voltage:, 0,6/1 kV

Construction 

  1. Solid or stranded copper conductor
  2. XLPE insulation
  3. Halogen Free filler
  4. EVA/PR based Outer sheath

Application
Hotels, schools, tunnels, high-rise buildings, hospitals, power plants, data processing centers and business centers where people are densely populated, and fire-sensitive areas

Nominal
cross-section
Overall diameter
(Approx)
Net Weight
(Approx)
Delivery
Lenght
Conductor DC
Resistance
Current carrying capacity in
mm² mm kg/km m ohm/km In conduit at 20°C A In air at 30°C A
5x1,5 12 190 1000 12,1 21 18
7x1,5 13 230 1000 12,1 18 16
10x1,5 15 320 1000 12,1 15 13
12x1,5 16 370 1000 12,1 14 13
14x1,5 17 400 1000 12,1 14 12
19x1,5 18,5 500 1000 12,1 12 11
21x1,5 19,5 550 1000 12,1 11 10
24x1,5 21,5 600 1000 12,1 11 10
30x1,5 23 750 1000 12,1 10 9
40x1,5 25 950 1000 12,1 9 8
48x1,5 28 1100 1000 12,1 8 8
61x1,5 31 1650 1000 12,1 8 7
5x2,5 13 250 1000 7,41 28 24
7x2,5 14 300 1000 7,41 24 21
10x2,5 17 430 1000 7,41 20 18
12x2,5 18 500 1000 7,41 19 17
14x2,5 19 550 1000 7,41 18 16
19x2,5 21 700 1000 7,41 16 14
21x2,5 22 750 1000 7,41 15 14
24x2,5 24 850 1000 7,41 14 13
30x2,5 26 1050 1000 7,41 13 12
40x2,5 28 1400 1000 7,41 12 11
48x2,5 31 1650 1000 7,41 11 11
61x2,5 34 2050 1000 7,41 10 10